Component |
Current
Status |
Recommendations |
Cost |
|
General
Exterior |
The
Wood County Holding Facility was constructed in 1974. It is not on the National
Historic Register. The building is one story and is approximately 22,000
square feet . The
foundation is concrete and there is no apparent settlement. The
general exterior of the building is in good condition. |
The
regional jail is in place in We recommend remodeling approximately half of the
existing holding facility for storage and offices. This remodeling is to include all life and
safety, |
$1,441,000 |
|
Exterior
Walls |
The exterior walls are tilt-up, prefabricated
concrete panels. The caulking between the panels is deteriorating. There are
no visible cracks in the walls. P33 |
Caulk
between panels. |
$15,000 |
|
Roof |
The
roof is flat with a rubber membrane. It appears to be in good condition. |
|
|
|
Windows
and Doors |
The windows are aluminum framed with Lexan
bulletproof glass. They are original to the building’s construction. They are
in good condition. P33 |
|
|
|
Fire
Safety |
There
is a fire alarm system but no sprinkler system. There are illuminated exit
lights and emergency lights with power back up. The stairs are enclosed with
fire rated doors and walls. They are free from obstructions. There is storage
under the stairs. The exit doors swing in the direction of the exit. The
doors are equipped with panic hardware. No pictures were taken due to
security. |
No
sprinkler system needed. |
|
|
There
is no |
The
remodeled portion shall become |
See General Exterior Above |
Structure
|
No
structural concerns were noted during the inspection. |
|
|
|
Security |
The
building has a security system. There are no walk through metal detectors.
There is a closed circuit TV system. |
No
walk through metal detectors needed. |
|
|
Electrical |
The
main distribution panel is a 1200 amp ITE. It is in good condition with some
corrosion on the cover. There are several other sub panels that are in good
condition but are corroding. There is a generator in good condition. P18
The lighting is both fluorescent and incandescent and is in excellent
condition. P16
The electric service is underground. |
|
|
|
Mechanical |
A
Smith gas boiler that is in excellent condition supplies the heat. P1 There is a Trane condensing unit on the
roof. It is in excellent condition. There is also a Trane chiller that is in
poor condition but still works. P20 The
circulating pumps are in poor condition. |
Replace
the chiller and circulating pumps. The HVAC system will have to be modified
for the proposed offices but some of the equipment can be reused. The cost of
mechanical modifications is include in “General Exterior” above. |
See General Exterior Above |
|
Work
Safety |
No
work safety issues were noted during the inspection. |
|
|
|
Space
requirements |
The
need for space has been reduced due to the regional jail facility. The unused
portion of this building can be remodeled for offices and storage to
accommodate the growing complex. See “General Exterior” above. |
|
|
|
Subtotal |
|
|
$1,456,000 |
|
Soft
Costs |
Professional
fees, permits, surveys, and studies |
20% |
291,200 |
|
Total |
|
|
$1,747,200 |