Braxton County Courthouse Annex Detail Report

 

Component

Current Status

Recommendations

Cost

General Exterior

The original date of the Braxton County Courthouse’s Annex construction was noted to be in the 1940’s.  The approximate size of the Annex is 12,000 square feet and is four stories plus a basement, and two small towers.  One tower is the elevator shaft and the other is the stairway access to the roof, (P1, P2, P3, P4, P5).  The general exterior is in very good condition.

 

 

 

 

 

 

 

Exterior Walls

The foundation is concrete block, (P6) and the exterior walls are brick.  There is no evidence of settlement of the foundation.  There is one crack in the exterior wall located on the Southwest corner of the building traveling from the 3rd to the 4th floor, (P7).  Tar has been spilled down the North side of the building, (P8).  Water stains have occurred underneath most of the windows on each floor, (P1). 

 

Clean and seal brick walls.

$20,000

Roof

The roof on the Annex is a low slope (relatively flat) with a rubber membrane that had been replaced.  No approximation could be given on the replacement date, (P9, P10).  The roof is in very good condition.

 

 

 

Windows and Doors

 

 

 

 

 

 

 

 

 

 

 

 

ADA

The windows throughout the annex are new.  They had been replaced within the last 4 years.  They are in very good condition with aluminum frames, thumb latches, and double pane glass.  The front entrance doors for the Annex are steel and glass with static panic hardware installed.  The front door is in excellent shape, (P14).  There is also a fire escape door for each floor heading out the north side of the building, (P15).  This fire escape is not adequate because it is not covered.  The fire doors have panic hardware installed.  The front and fire exit doors swing out from the building.

 

The Annex shares parking with the courthouse. The main entrance is two steps and needs a ramp to access the first floor but there is an elevator to access the other floors.

 

The toilets do not meet ADA requirements.

 

The doors need lever handles and ADA signage.

Provide an enclosed stair tower in place of the fire escape.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Entrance ramp

 

Renovate toilet to ADA standards

 

Install lever handles on all public access doors

 

Install ADA signage throughout the building

$40,000

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

$40,000

 

$20,000

 

$18,750

 

$2,500

Fire Safety

The Annex’s old fire alarm system is no longer in service, (P16).  Currently the building doesn’t have means of fire detection.  The only means of fire suppression is the extinguishers located throughout the floors of the building.  There are two means of egress from each floor.

 

Install a fire alarm system.

 

Install a Sprinkler system

$5,000

 

$30,000

Structure

 

All the walls of the building are poured concrete with reinforced steel throughout, (P18).  There is water damage to the walls on the fourth floor located in the west side room, (P19).  There is water damage located in the east side room on the fourth floor but no pictures were available since the door was locked.  There is also water damage and cracks located in the stairs the exit to the roof, (P20).  There is noticeable sagging in the ceiling of the fourth floor.

It was noted that there is cracking in the wall on the inside room of the 3rd floor.  This is the same area where the outside crack is located on the Southwest corner.  No inside pictures were available since the door was locked. 

 

A structural evaluation should be completed to determine the cause of the sagging and water damage that is taking place on the fourth floor ceiling as well as the crack from the 3rd to 4th floor.

 

Patch the plaster that has been damaged by water after the structure is repaired.

$10,000

 

 

 

$2,000

Security

There is a closed circuit television system in the building, (P21).  There are panic buttons located in the Magistrate Courtroom and in various other offices in the building.  There are no guards, metal detectors, alarm systems, or bulletproof protection located in the building. 

 

Provide limited access to the building with:

     Metal Detector

     X-ray machine

     Security System with glass breakage alarms

     Ballistic material for bench

     Card Access System

     Alarmed exit doors for other exits

    

 

$4,500

$35,000

$8,000

$1,500

$9,000

$9,000

Electrical

The main electrical service for the Annex entered the east side from a pole-mounted set of transformers located across the street from the South side of the building, (P22).  This service is distributed from a Square D 208Y / 120V, 600 A, main distribution panel located in the basement, (P23).  The electrical service is then distributed to panels throughout the building; some panels have been painted over and have missing covers and latches, (P24).  There is also a small 5 KVA Wagner transformer located on the 2nd floor in good condition, (P25).  The electrical system is in fair condition with over loading problems reported when excessive appliances (i.e. space heaters) are plugged in.  There is a Kohler backup generator on the north side of the building for the 911 office.  This generator is good condition and is functioning properly.

 

The interior lighting (fluorescent and incandescent) in the building is adequate with no reported problems.  There are battery backup emergency lights located throughout the building.  There are exit lights located at the exits but do not light up properly.

 

Upgrade the electrical service to meet the current needs of the facility.  Repair/replace exit lights as required.  Replace lights as required.  Install locking electrical boxes and switches in the hall and courtroom.

$96,000

Mechanical

The Annex has a Burnham gas-fired boiler, (P27) located in the basement with one Barber Colman air handler located on each floor.  The boiler has excessive rust on the top of the casing but otherwise is in good operating condition. 

 

Cooling is handled by a Marley Cooling tower (which appears to be leaking) on the roof with a Technical System chiller in the basement in good operating condition.  There was a Carrier window unit cooling the 911 office.  This window unit was in good condition and in operating order.

 

There are a couple of window A/C units, which indicate that the building air conditioning system is not adequate.  There is also a concern that the cooling tower may be the cause of the sagging 4th floor ceiling.  Revise the Building cooling system to eliminate the cooling tower on the roof and eliminate the window units.

$85,000

Work Safety

The main electrical panel located in the basement requires blanks to be installed in the breaker openings, (P23).  Several electrical panels are missing doors and proper locking hardware.

 

 

 

Space requirements

These issues are covered under the courthouse detail report.

 

 

Sub Total

 

 

$436,250

Soft Costs

Professional fees, permits, surveys, and studies

20% of total

$87,250

Total Cost

 

 

$523,500

 

 

Braxton Index Page